CVE-2023-25914: Danfoss AK-SM 800A Series · Path traversal
Exploitation: In the wild · CVSS 8.8 High · Authenticated · Published 2023-08-21
Description
Due to improper restriction, authenticated attackers could retrieve and read system files of the underlying server through the XML interface. The information that can be read can lead to a full system compromise.
Enclave's analysis
Danfoss AK-SM800A refrigeration controllers before firmware 3.3 let an attacker pull arbitrary system files, including the password file, through the XML management interface with a simple path-traversal request. The finder's own advisory shows a bare HTTP request doing this with no login at all, which undercuts the official score's assumption of low-privilege access. Chained with a second Danfoss bug it gives root-level code execution, and CISA has now added it to its Known Exploited Vulnerabilities list. Patch to 3.3 or pull the XML interface off the internet — this product line keeps surfacing fresh unauthenticated bugs.
Fix
Upgrade Danfoss AK-SM800A to 3.3. No fixed version is listed for AK-SM800A; follow the vendor advisory.
Affected versions
| Product | Vulnerable | Fixed in |
|---|---|---|
| AK-SM800A | < 3.3 | Not listed |
| Danfoss AK-SM800A | < 3.3 | 3.3 |